| Brand | ROCKWILL |
| Model NO. | 363/420kV Hybrid Gas Insulated Switchgear |
| Rated voltage | 420kV |
| Rated short-time withstand current | 63kA |
| Series | ZF28 |
Product Description
ZF28-420 Hybrid Gas Insulated Switchgear is a three-phase AC high-voltage electrical equipment, which is designed for controlling, measuring, protecting, and switching power transmission lines, and can be combined into the required main wiring arrangement according to user requirements.
Features
Product Parameters
| Rated voltage | 363/420 kV |
| Rated frequency | up to 5000 A |
| Rated short-duration power-frequency withstand voltage(1 min,effective value)Phase to phase,phase to ground | 520 kV |
| Rated short-duration power-frequency withstand voltage(1 min,effective value)Across isolating distance | 520+210 kV |
| Rated lightning impulse withstand voltage(peak value)Phase to phase,phase to ground | 1175 kV |
| Rated lightning impulse withstand voltage(peak value)Across isolating distance | 1175+295 kV |
| Rated short-time withstand current | up to 63 kA |
| Rated duration of short-circuit | 3 s |
| Rated peak withstand current | up to 171 kA |