| Brand | ROCKWILL |
| Model NO. | Bypass Electric SF6 Load break Switch 12kV 24kV |
| Rated voltage | 12kV |
| Rated normal current | 400A |
| Rated frequency | 50/60Hz |
| Series | LBS |
Product Overview
The Bypass Electric SF6 Load Switch is a high-performance, durable switching device engineered for medium-voltage power distribution systems, featuring low power loss, excellent heat dissipation, and strong overload capacity. It integrates advanced SF6 insulation and arc-extinguishing technology with a specialized bypass design, enabling safe and efficient load transfer and maintenance without power interruption.Designed for global industrial, commercial, and utility applications, this switch boasts superior corrosion resistance, stable mechanical performance, and flexible operation modes, fully complying with international IEC standards. It is an ideal solution for power distribution networks requiring reliable bypass switching, easy maintenance, and enhanced safety protection.
Core Advantages & Key Features
With a focus on durability, flexibility, and safety, the switch offers distinct competitive advantages that meet the demands of overseas purchasers:
Key Technical Specifications
|
1
|
Structure form
|
Co - box type
|
||
|
2
|
Arc - extinguishing medium / Insulating medium
|
SF₆ arc - extinguishing / SF₆
|
SF₆ arc - extinguishing / SF₆
|
|
|
3
|
Rated voltage (kV)
|
12
|
24
|
|
|
4
|
Rated current (A)
|
200 / 400 / 630
|
200 / 400 / 630
|
|
|
5
|
Temperature rise test current
|
1.1Ir
|
1.1Ir
|
|
|
6
|
Rated 1 - minute power - frequency withstand voltage (kV)
|
Relative to ground / Between phases
|
45
|
55
|
| Between breaking points |
65
|
79
|
||
|
7
|
Rated short - time withstand current and duration (kA/s)
|
20 / 4
|
20 / 4
|
|
|
8
|
Rated peak withstand current (kA)
|
50
|
50
|
|
|
9
|
Rated short - circuit making current (kA)
|
20
|
20
|
|
|
10
|
Rated short - circuit breaking current (kA)
|
50
|
50
|
|
|
11
|
Main - circuit resistance (μΩ)
|
≤130
|
≤130
|
|
|
12
|
Mechanical stability (times)
|
≥5000
|
≥5000
|
|
|
13
|
Phase spacing (mm)
|
132 ± 2mm
|
132 ± 2mm
|
|
|
14
|
Rated current breaking times (times)
|
≥400 times
|
≥400 times
|
|
|
15
|
Operating mode
|
Electric, with manual operation function
|
||
|
16
|
Operating voltage (V)
|
DC24
|
||
|
17
|
Different periods of opening and closing (ms)
|
≤3
|
||
|
18
|
Closing speed (m/s)
|
1.8 ± 0.4 (m/s)
|
||
|
19
|
Opening speed (m/s)
|
1.8 ± 0.4 (m/s)
|
||
|
20
|
Opening and closing time (ms)
|
≤1000
|
||
|
21
|
Breaking gap distance (mm)
|
≥40
|
||
|
22
|
SF₆ gas annual leakage rate
|
≤0.1%
|
||
|
23
|
Enclosure protection class
|
IP67
|
||
|
24
|
Service life of the switch
|
30 years
|
||
|
25
|
Transportation weight (kg)
|
95
|
||
|
Current sensor
|
Ratio
|
Phase current: 600A / 1A; 1000A / 1A
|
||
|
Accuracy class
|
Phase current: Protection 5P10 class, Measurement 0.5 class
|
|||
|
Capacity
|
cT: ≥1VA
|
|||
|
Voltage sensor
|
Ratio
|
A / B / C; R / S / T; 6 - phase voltage sensors: Phase voltage V / 0.4 - - 37V (ratio selectable)
|
||
|
Accuracy class
|
0.5 class
|
|||
Application Scenarios
With its bypass function, durable corrosion-resistant design, and flexible operation, the Bypass Electric SF6 Load Switch is widely used in global medium-voltage power distribution systems, especially suitable for: