占位边距

Products

China recloser,transformer,switchgear,EV charger,Digital power station Manufacturer

1100kV UHV SF6 Circuit Breaker
  • 1100kV UHV SF6 Circuit Breaker
Key attributes
Brand ROCKWILL
Model NO. 1100kV UHV SF6 Circuit Breaker
Rated voltage 1100KV
Rated normal current 4000A
Series LW10B
Product descriptions from the supplier
Description

Description

SF6 circuit-breaker is a double-column four-fracture form, with a shunt capacitor and a closing resistor at interrupter chamber breaks; The circuit-breaker has compact structure, small arc extinguishing chamber, high contact speed, stable and reliable performance, long service life and high comprehensive technical and economic index.

SF6 circuit-breaker is outdoor three-phase AC 50Hz UHV transmission equipment, which is used to control, measure, protect and switch transmission lines in the power system with a rated voltage of 1000 kV. It can also be used to meet the capacitive current of the filter bank and capacitor bank to realize the control and protection of the filter bank and capacitor bank. The circuit-breaker is equipped with ABB HMB-8.12 compact spring hydraulic operating mechanism for division, closing and automatic reclosing. Each column has an independent hydraulic system, which can be operated in separate phases to realize single-phase automatic reclosing. Through the electrical linkage can also be three-phase linkage operation to achieve three-phase automatic reclosing.

Main Features

  • Double column four fracture form, interrupter chamber fracture parallel capacitor and closing resistor, Cut back on oil.

  • The mechanical reliability of the product is good, to ensure the mechanical life of 10,000 times.

  • The circuit breaker structure is compact, the arc extinguishing chamber is small, the contact movement speed is high, the performance is stable and reliable, the service life is long, the comprehensive technical and economic indicators are high.

Technical parameter

1719906238272.png

 

Documentation Resource Library
Live Tank Breakers Catalog
Restricted.
Live Tank Breakers Catalog
Catalogue
English
Consulting
Consulting
FAQ
Q: What are the differences between this product and similar products from ABB/Siemens?
A:

The LW10B \ lLW36 \ LW58 series products in the sample booklet are porcelain column SF ₆ circuit breakers based on the ABB'LTB series improvement, with voltage coverage of 72.5kV-800kV, using Auto Buffer ™ Self powered arc extinguishing technology or vacuum arc extinguishing technology, integrated spring/motor driven operating mechanism, supports various customized services, covering 40.5-1100kV full voltage levels, with outstanding modular design and strong customization ability, suitable for projects that require flexible adaptation to different power grid architectures. Made in China, with fast global service response speed, high logistics efficiency, and high reliability at a reasonable price.

Q: What are the core differences between live tank circuit breakers and tank circuit breakers?
A:
  1. The core differences between porcelain column circuit breakers and tank circuit breakers—two main structural types of high-voltage circuit breakers—lie in six key aspects.
  2. Structurally, porcelain column types are supported by porcelain insulation pillars, with open-layout components like arc extinguishing chambers and operating mechanisms. Tank types use metal-sealed tanks to encapsulate and highly integrate all core parts.
  3. For insulation, the former relies on porcelain pillars, air, or composite insulating materials; the latter combines SF₆ gas (or other insulating gases) with metal tanks.
  4. Arc extinguishing chambers are mounted on the top or pillars of porcelain columns for the former, while built inside metal tanks for the latter.
  5. In application, porcelain column types suit outdoor high-voltage distribution with a dispersed layout; tank types adapt flexibly to indoor/outdoor scenarios, especially space-constrained environments.
  6. Maintenance-wise, the former’s exposed components enable targeted repairs; the latter’s sealed structure reduces overall maintenance frequency but requires full inspections for local faults.
  7. Technically, porcelain column types offer intuitive structure and strong anti-pollution flashover performance, while tank types boast excellent sealing, high SF₆ insulation strength, and superior resistance to external interference.
Q: What is a live tank circuit breaker? What voltage level is it suitable for they?
A:

live tank circuit breaker is a structural form of high-voltage circuit breaker, which is characterized by the use of ceramic insulation pillars to support key components such as arc extinguishing chamber and operating mechanism. The arc extinguishing chamber is usually arranged on the top or pillar of the ceramic pillar. It is mainly suitable for medium and high voltage power systems, with voltage levels covering the range of 72.5 kV to 1100 kV. live tank circuit breakers are common control and protection equipment in outdoor distribution devices such as 110 kV, 220 kV, 550 kV, and 800 kV substations.

Related Products
Related Solutions
Inquiry
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!