| Brand | ROCKWILL |
| Model NO. | Air Insulated Switchgear with Withdrawable Vacuum Circuit Breaker |
| Rated voltage | 40.5kV |
| Rated frequency | 50/60Hz |
| Series | JPW2 |
| Rated voltage | kV | 30, 36, 38, 40.5 | ||||||
| Rated frequency | HZ | 50/60 | ||||||
| Rated 1 min power frequency withstand voltage | kV |
70, 95 | ||||||
| Rated lightnig impulse withstand voltage | 170, 185 | |||||||
| Rated miain busbar current | A | 630, 1250, 2000, 2500, 3150 | ||||||
| Rated circuit breaker current | 630, 1250, 2000, 2500, 3150 | |||||||
| Rated short -time withstand current | kA | 25 ,31.5 | ||||||
| Rated duration of short-circuit | S | 3 | ||||||
| Peak withstand current | kA | 63 , 80 | ||||||
| Rated breaking current | 25 , 31.5 | |||||||
| Rated making current(peak value) | 63 ,80 | |||||||
| Standard Dimenson (W) | mm | 1200 | ||||||
| Standard Dimenson (D) | 2500, 2800 | |||||||
| Standard Dimenson (H) | 2400 | |||||||
| Mass | KG | up to 2000 | ||||||
| Degree of protection | IP3X IP4X | |||||||