| Brand | ROCKWILL |
| Model NO. | Indoor Medium Voltage SF6 Circuit Breaker 12kV 40.5kV |
| Rated voltage | 40.5kV |
| Rated normal current | 1250A |
| Rated frequency | 50/60Hz |
| Series | FEP |
Product Introduction
The FEP Indoor SF6 Circuit Breaker is the latest generation of high-voltage switching equipment developed based on mature and reliable SF6 interruption technology. It fully complies with international standards including DL and IEC, making it a reliable choice for global medium and high-voltage power distribution projects.Designed for seamless compatibility, this SF6 circuit breaker is interchangeable when matched with AMS switchgear and can be easily and reliably integrated with most mainstream switchgear available on the global market. It is widely used as a core switching component in indoor high-voltage power systems, delivering stable performance and strong adaptability.
Core Advantages & Technical Highlights
Key Technical Specifications
|
No.
|
|
Parameter
|
|
Unit
|
Value 1
|
Value 2
|
|---|---|---|---|---|---|---|
|
1
|
Rated Voltage
|
kV
|
40.5
|
12
|
||
|
2
|
Rated Frequency
|
Hz
|
50/60
|
-
|
||
|
3
|
Rated Current
|
A
|
1250/1600/2000/2500/3150*
|
1250
|
||
| 4 |
Insulation Level
|
Rated Power - frequency Withstand Voltage (1min)
|
To ground and between phases
|
kV
|
95
|
42
|
|
Rated Power - frequency Withstand Voltage (1min)
|
- Between breaks
|
kV
|
118
|
48
|
||
|
Rated Lightning Impulse Withstand Voltage
|
- To ground and between phases
|
kV
|
185
|
75
|
||
|
Rated Lightning Impulse Withstand Voltage
|
- Between breaks
|
kV
|
215
|
85
|
||
|
Short - time Power - frequency Withstand Voltage of Auxiliary and Control Circuits
|
kV
|
2
|
2
|
|||
|
5
|
Partial Discharge
|
pC
|
≤5
|
-
|
||
|
6
|
Rated Short - circuit Breaking Current
|
kA
|
31.5、40
|
31.5
|
||
|
7
|
Rated Short - circuit Making Current (Peak Value)
|
kA
|
80、100
|
31.5
|
||
|
8
|
Rated Out - of - phase Breaking Current
|
kA
|
7.9、10
|
7.9
|
||
|
9
|
Rated Open - circuit Breaking Current of Asynchronous Phases
|
kA
|
27.4、34.4
|
27.4
|
||
|
10
|
Rated Peak Withstand Current
|
kA
|
80、100
|
80
|
||
|
11
|
Rated Short - time Withstand Current
|
kA
|
31.5、40
|
31.5
|
||
|
12
|
Rated Short - circuit Duration
|
s
|
4
|
|||
|
13
|
Rated Breaking Current of Transformer Bank Opposite to the Circuit Breaker
|
A
|
1250
|
|||
|
14
|
Rated Cable Charging Breaking Current
|
A
|
50
|
25
|
||
Application Scenarios
Procurement Support for Overseas Buyers
We provide comprehensive support for overseas purchasers to ensure smooth procurement, installation and use: