| Brand | ROCKWILL |
| Model NO. | Indoor Metal-Clad with Drawable Switchgear for Primary Distribution |
| Rated voltage | 12kV |
| Rated frequency | 50/60Hz |
| Series | Kyn28 |
Product Description
KYN28A-12 Steel-clad Removable-type Metal-enclosed Switchgear (hereinafter called switchgear for short) is applicable in the power system of three phases 50/60HZ. which is used to receive and distribute power as well as control. protect and moniter the circuit of power plant, substation and industrial and mining enterprises and high-rise buildings.
KYN28A-12 switchgear has the function of preventing various wrong operations including preventing loading mobile handcart, preventing grounding switch to circuit the breaker in closed position, preventing to close the charged grounding switch and preventing straying into charged compartment and other functions. Switchgear is equipped with excellent mid-set type of VS1, VD4 series high voltage vacuum circuit breaker and enclosed type vacuum circuit breaker. The secondary loop configuration of the switchgear is advanced and reliable control protection devices: Busbar with heat insulation materials or the insulation of the epoxy coating methods, optimizes the electrode shape and compacts the structure. The switchgear is safe and reliable power distribution equipment with advanced technology. stable performance, reasonable structure and easy usage.
Service condition
Main characteristics
Adopt an intelligent switch cabinet operating system
2.Adopt intelligent information processing system to diagnose and monitor the failure precursor of the switchgear body
3. Intelligent anti-misoperation operating system
4. Intelligent function of secondary circuit
Intelligent measurement, signal, protection, control and movement.
5. Remembrance of grid failure
Wave recording, login, simulation replay and fault recording, provide analysis data.
Technical Sheet
| Technical specification | Unit | Data | ||
| Rated voltage | kV | 3.6,7.2,12 | ||
| Rated frequency | Hz | 50/60 | ||
| Circuit breaker rated current | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 | ||
| Rated current of switchgear | A | 630, 1250, 1600, 2000, 2500, 3150, 4000 | ||
| Rated short-time withstand current (4s) | kA | 16,20,25,31.5,40,50 | ||
| Rated peak withstand current (peak value) | kA | 40,50,63,80,100,125 | ||
| Rated short-circuit breaking current | kA | 16,20,25,31.5,40,50 | ||
| Rated short-circuit making a current (peak value) | kA | 40,50,63,80,100,125 | ||
| Rated insulation level | 1min power frequency withstand voltage | interpolar, Between poles | kV | 24,32,42 |
| between open contacts | kV | 24,32,48 | ||
| Lightning impulse withstand voltage (peak value) | interpolar, Between poles | kV | 40,60,75 | |
| between open contacts | kV | 46,70,85 | ||
Main primary part
SF6 load break switch
SF6 load break switch used in the modular switchgear has multiple functions for 3 working positions, combined with grounding switch and isolation switch. With 0.045 Map SF6 gas filled in a fully sealed epoxy resin enclosure that make its structure enhanced and good insulation performance.
Thanks to its design, it ensures the quality and reliability for its's proper operation in switchgear control.
Its's mechanical and electrical interlocking systems between the load break switch and the earthing switch, possibility of a wrong-man oeuvre is prevented by these interlocking systems.

Vacuum circuit breaker
The VS1 (VN) vacuum circuit breakers are designed with solid sealed pole type, side-mounted installed, and high mechanical stability. It can be used to store energy with AC and DC power supply, and also be used by manually. It has the advantages of compact size, strong breaking capacity, high insulation strength, no pollution, no danger of explosion and etc.