| Brand | ROCKWILL |
| Model NO. | Outdoor High-Voltage AC SF6 Bypass Load break Switch 12kV 24kV |
| Rated voltage | 12kV |
| Rated normal current | 200A |
| Rated frequency | 50/60Hz |
| Series | LBS |
Product Overview
The Outdoor High-Voltage AC SF6 Bypass Load break Switch is a high-reliability, durable switching device engineered for outdoor medium and high-voltage AC power distribution systems. Integrating advanced SF6 gas insulation and arc-extinguishing technology with a specialized bypass design, it is designed to realize safe load transfer and equipment maintenance without power interruption, while boasting low power loss, excellent heat dissipation, and strong overload capacity.Compliant with international IEC standards, this switch features corrosion-resistant 304 stainless steel housing, stable mechanical performance, and flexible operation modes, making it an ideal core component for global urban and rural power grids, industrial facilities, and commercial infrastructure projects. It perfectly meets the procurement needs of overseas clients for high-quality, low-maintenance, and safe bypass switching equipment.
Core Features
Focusing on durability, stability, and operability, the switch has distinct competitive advantages that align with the core demands of overseas purchasers:
Key Technical Specifications
|
1
|
Structure Form
|
Common Box Type
|
Common Box Type
|
|
|
2
|
Arc - extinction Medium / Insulation Medium
|
SF6 arc - extinction / SF6
|
SF6 arc - extinction / SF6
|
|
|
3
|
Rated Voltage (kV)
|
12
|
24
|
|
|
4
|
Rated Current (A)
|
200/400/630
|
200/400/630
|
|
|
5
|
Temperature - rise Test Current
|
1.1Ir
|
1.1Ir
|
|
|
6
|
Rated Power - frequency Withstand Voltage for 1min (kV)
|
Relative Ground/Phase - to - phase
|
45
|
65
|
|
Breaker Gap
|
55
|
79
|
||
|
7
|
Rated Short - time Withstand Current and Duration (kA/s)
|
20/4
|
20/4
|
|
|
8
|
Rated Peak Withstand Current (kA)
|
50
|
50
|
|
|
9
|
Rated Short - circuit Making Current (kA)
|
20
|
20
|
|
|
10
|
Rated Short - circuit Breaking Current (kA)
|
50
|
50
|
|
|
11
|
Main Circuit Resistance (μΩ)
|
≤130
|
≤130
|
|
|
12
|
Mechanical Stability (times)
|
≥5000
|
≥5000
|
|
|
13
|
Phase Spacing (mm)
|
132 ± 2mm
|
132 ± 2mm
|
|
|
14
|
Rated Current Making and Breaking Times (times)
|
≥400 times
|
≥400 times
|
|
|
15
|
Operating Mode
|
Electric, with Manual Operation Function
|
||
|
16
|
Operating Voltage (V)
|
DC24
|
||
|
17
|
Different Periods of Opening and Closing (ms)
|
≤3
|
||
|
18
|
Closing Speed (m/s)
|
1.8 ± 0.4 (m/s)
|
||
|
19
|
Opening Speed (m/s)
|
1.8 ± 0.4 (m/s)
|
||
|
20
|
Opening and Closing Time (ms)
|
≤1000
|
||
|
21
|
Breaker Gap Distance (mm)
|
≥40
|
||
|
22
|
SF6 Gas Annual Leakage Rate
|
≤0.1%
|
||
|
23
|
Protection Class of Switch Housing
|
IP67
|
||
|
24
|
Service Life of Switch
|
30 years
|
||
|
25
|
Transportation Weight (kg)
|
95
|
||
|
Current Sensor
|
Rated Current Ratio
|
Phase Current: 600A/1A; 1000A/1A
|
||
|
Accuracy Class
|
Phase Current: Protection 5P10 class, Measurement 0.5 class
|
|||
|
Voltage Sensor
|
Transformation Ratio
|
A/B/C; R/S/T; 6 - phase voltage sensors: Phase Voltage V / 0.4 - 37V (transformation ratio selectable)
|
||
|
Accuracy Class
|
0.5 class
|
|||
Application Scenarios
With its specialized bypass function, durable corrosion-resistant design, and flexible operation, the switch is widely used in global outdoor high-voltage AC power distribution systems, especially suitable for: