| Brand | ROCKWILL |
| Model NO. | 126kV 145kV high voltage SF6 circuit breaker |
| Rated voltage | 145kV |
| Rated normal current | 3150A |
| Rated frequency | 50/60Hz |
| Rated short circuit breaking current | 40kA |
| Series | LW36-126(145) |
Product introduction
The LW36-126(145)(W) circuit breaker is a cutting-edge electrical device designed for versatile applications in power systems. Suitable for single-phase operation, three-phase electrical linkage, and three-phase mechanical linkage, this breaker is optimized for grid frequencies of 50/60Hz in both neutral-grounded and neutral-ungrounded systems. It excels in demanding scenarios, featuring C2-level capabilities for back-to-back capacitor bank switching, no-load line-charging breaking, and no-load cable-charging breaking—meeting the highest international standards for reliability and performance.
Suitable for single-phase/three-phase (electrical/mechanical) operation in 50/60Hz grids (neutral-grounded/ungrounded systems). Meets C2-level standards for back-to-back capacitor bank, no-load line/cable switching.
Features
Arc Extinguishing: SF6 gas + self-energy technology for low power consumption, 40kA short-circuit breaking (22x consecutive without maintenance).
Mechanism: Spring actuating system with 10,000-cycle mechanical life (M2 class), low noise (<65dB), and compact design (30% smaller than traditional models).
Reliability:
Seismic: Complies with IEEE693-2018 1.0g and ETG Chile standards.
Insulation: Creepage distance >31mm/kV, operates at ≤3000m altitude, anti-pollution design.
Sealing: SF6 annual leakage rate <0.5%, strict dehumidification (moisture content below industry norms).
Materials
Zinc-base alloy valve plates for stable gas dynamics.
Imported PTFE spouts with high ablation resistance.
Stainless steel mechanism cases + hot-galvanized fasteners for corrosion resistance.
Maintenance: ≥10-year maintenance-free cycle, 25,000+ global installations, optional phase closing device.
Specifications
Voltage: 126kV (145kV withstand).
Current-carrying: Passed 3780A temperature-rise test with safety margins.
Environment: -30°C to +70°C, IP65 protection.
Standards: IEC 62271-100, GB 1984, DL/T 402.
Main technical parameters

Instructions on placing orders
Model and format of the circuit breaker.
Rated electrical parameters (voltage, current, breaking current, etc).
Working conditions for using (environment temperature, altitude, and environment pollution level).
Rated control circuit electrical parameters (Rated voltage of energy-store moter and Rated voltage of opening, closing coil).
Names and quantities of spare items needed, parts and special equipment and tools (to be otherwise ordered).
The wire connecting direction of the primary upper terminal.
The LW10B \ lLW36 \ LW58 series products in the sample booklet are porcelain column SF ₆ circuit breakers based on the ABB'LTB series improvement, with voltage coverage of 72.5kV-800kV, using Auto Buffer ™ Self powered arc extinguishing technology or vacuum arc extinguishing technology, integrated spring/motor driven operating mechanism, supports various customized services, covering 40.5-1100kV full voltage levels, with outstanding modular design and strong customization ability, suitable for projects that require flexible adaptation to different power grid architectures. Made in China, with fast global service response speed, high logistics efficiency, and high reliability at a reasonable price.
live tank circuit breaker is a structural form of high-voltage circuit breaker, which is characterized by the use of ceramic insulation pillars to support key components such as arc extinguishing chamber and operating mechanism. The arc extinguishing chamber is usually arranged on the top or pillar of the ceramic pillar. It is mainly suitable for medium and high voltage power systems, with voltage levels covering the range of 72.5 kV to 1100 kV. live tank circuit breakers are common control and protection equipment in outdoor distribution devices such as 110 kV, 220 kV, 550 kV, and 800 kV substations.