Description
The 40.5kV Metalclad AC Enclosed Switchgear, Withdrawable Type is a high-performance medium-voltage solution engineered for robust, reliable power distribution in large-scale industrial facilities, utility substations, and high-voltage grids. Its robust metalclad enclosure ensures superior protection, while the withdrawable design enables efficient maintenance, making it a cornerstone for stable high-voltage power management.
Application: In the system of 50Hz, 40.5kV, for power distribution, circuit control and protection.
Standards: IEC 62271-200
Product Advantages
- High-Voltage Resilience:Designed for 40.5kV systems, it withstands high electrical stress with advanced insulation, ensuring safe operation in demanding high-voltage networks.
- Withdrawable Mechanism:Critical components (e.g., circuit breakers) can be easily withdrawn, allowing swift maintenance or replacement without disrupting the entire system, reducing downtime.
- Robust Metalclad Protection:All-steel enclosure provides IP-rated defense against dust, moisture, and physical impact, enhancing durability in harsh industrial environments.
- Enhanced Safety Interlocks:Multi-layer mechanical and electrical interlocks prevent misoperations (e.g., accidental closing under load), safeguarding personnel and equipment.
- Scalable Configuration:Adaptable to various grid setups (incoming, outgoing, transformer connections), supporting flexible integration into complex power distribution architectures.
- Low Lifecycle Costs:Durable construction and minimized maintenance needs (thanks to withdrawable parts) reduce long-term operational expenses, ensuring cost efficiency.
Parameters
|
Item
|
|
Unit
|
Data
|
|
Rated voltage
|
kV
|
40.5
|
|
Rated current
|
Rated current of main bus bar
|
A
|
1250, 1600, 2000, (2500)
|
|
Rated current of matched VCB
|
A
|
1250, 1600, 2000, (2500)
|
|
1min power frequency withstand voltage
|
KV
|
95
|
|
Lightning withstand voltage
|
kV
|
185
|
|
Power frequency withstands voltage of auxiliary circuit and control circuit
|
V/1min
|
2000
|
|
Rated frequency
|
Hz
|
50
|
|
Rated short-circuit breaking current
|
kA
|
20, 25, 31.5
|
|
Rated short-time withstand current/ Rated short-circuit continuous time
|
kA/4s
|
20, 25, 31.5
|
|
Rated withstands current (peak)
|
kA
|
50, 63, 80*
|
|
Rated short-circuit making current
|
kA
|
50, 63, 80*
|
|
Rated voltage of control circuit
|
V
|
DC: 110, 220; AC: 110, 220
|
|
\multirow{2}{*}{Protection level}
|
Switchgear shell
|
IP3X
|
|
Compartments (door opened)
|
IP2X
|