SF6 GAS Insulated Auto Section Switch

  • SF6 GAS Insulated Auto Section Switch
Key attributes
Brand ROCKWILL
Model NO. SF6 GAS Insulated Auto Section Switch
Rated voltage 25.8kV
Rated normal current 400A
Series SGA
Product descriptions from the supplier
Description

Product Introduction

SF6 GAS Insulated automatic sectionalizer switch. Multi-point neutral grounding system. Can make or break malfunctioning areas of power distribution line. Minimizing the damage to customer facilities.

Features of SF6 GAS Insulated automatic sectionalizer 
  • High technic
    Small and light, which makes it easy to use
    Uses Puffer-type interruption method
    Available in a wide range of temperatures -20℃ ~ 40℃
  • Safety
    Safe operation in live wire
    Operation and opening can be viewed by eye – prevents accidents during maintenance
    Excellent arc interruption abilities
  • Easy installation
    Small and light, which makes it easy for installation
  • Overload protection
    In over current lock below 800A, it operates under inverse time characteristic.
  • Charged spring trip
    When the product is undergoing breaking operation according to T-C curve due to overloading, or if the backup protection is operating even if ASS wasn’t broken as overload has been removed, zero voltage will occur. Then, ASS will instantaneously release to isolate the line downstream of ASS.
  • Inrush-current blocking function
    When ASS has operated correctly (Current bigger than 10% but smaller than 100% of setting current) and has broken an opening motion and then proceeded to close, this function will stop ASS mistaking the inrush-current from downstream equipment and malfunctioning.
  • Over current locking funtion
    If a malfunction which is bigger than rated interrupting current (900A) occurs, the prouct will product the switch. If the current is biger than the lock current (800A±10%), the switch will lock. GASS will then be interrupted in zero voltage after malfunctioning current is removed by backup protection.
  • Service condition
    Surrounding temperature: maximum 40/Minimum 20℃
    Altitude: less than 1,000m

Technical Parameters

Classification Characteristics
Model SGA-4 A
Rated Voltage 25.8 kV
Rated Current 400 A
Rated Short-time Current 12.5 kA (rms). 1s
Rated Short Circuit Making Current  32.5 kA (peak)
Rated Breaking Current 880 A
Pick-up current Phase 50,70,100,140,200,300,400 A, BLOCK
Ground 25,35,50,70,100,150,200 A, BY-PASS
Insulating Material SF6 GAS
 
Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO