| Brand | ROCKWILL |
| Model NO. | Fast Electric SF6 Load break Switch 12kV 24kV 40.5kV |
| Rated voltage | 40.5kV |
| Rated normal current | 630A |
| Rated frequency | 50/60Hz |
| Series | LBS |
Product Overview
The 12kV Fast Electric Load Switch is a high-performance, intelligent switching device engineered for 12kV medium-voltage power distribution systems. It integrates advanced SF6 arc-extinguishing technology, fast-operating mechanisms, and built-in sensing components, featuring low power loss, excellent heat dissipation, and strong overload capacity. Designed for global power distribution projects, this switch delivers reliable performance in frequent switching scenarios, with minimal maintenance requirements and enhanced safety protection, fully complying with international IEC standards.Ideal for urban and rural distribution networks, industrial power systems, and smart grid applications, it excels in fast fault handling and accurate power parameter collection, providing a cost-effective and trustworthy solution for overseas purchasers.
Core Advantages
Key Technical Specifications
|
Name
|
Unit
|
LBS-12
|
LBS-24
|
LBS-40.5
|
|||
|---|---|---|---|---|---|---|---|
|
Rated Voltage
|
kV
|
12
|
24
|
40.5
|
|||
|
Rated Current
|
A
|
630
|
630
|
630
|
|||
|
Rated Frequency
|
Hz
|
50/60
|
50/60
|
50/60
|
|||
|
Insulation Level
|
Fracture Insulation
|
Power Frequency (Dry/Wet)
|
kV
|
48
|
79
|
110
|
|
|
Test Voltage (Peak Value)
|
|
85
|
145
|
215
|
|||
|
Insulation Level to Ground and Between Phases
|
Power Frequency
|
Dry Test
|
kV
|
42
|
64
|
95
|
|
|
Wet Test
|
kV
|
34
|
50
|
70
|
|||
|
Lightning Impulse Withstand Voltage (Peak Value)
|
kV
|
75
|
125
|
185
|
|||
|
Breaking Capacity
|
Rated Breaking Current
|
A
|
630
|
630
|
630
|
||
|
Rated Maximum Breaking Current (Locked Rotor Current)
|
A
|
900
|
900
|
900
|
|||
|
Rated Thermal Stable Current (RMS)
|
kA
|
20
|
20
|
20
|
|||
|
Rated Thermal Stable Time
|
s
|
4
|
4
|
4
|
|||
|
Rated Short-Circuit Making Current/Peak Current
|
kA
|
50
|
50
|
50
|
|||
|
Mechanical Characteristics
|
Direct Energy Storage Mechanism (M)
|
Closing Time
|
ms
|
700-1000
|
|||
| Opening Time |
ms
|
700-1000
|
|||||
|
Pre-Energy Storage Mechanism (K)
|
Closing Time
|
ms
|
35-70
|
||||
|
Opening Time
|
ms
|
35-70
|
|||||
|
Closing Speed
|
m/s
|
1.8 ± 0.4
|
1.8 ± 0.4
|
1.8 ± 0.4
|
|||
|
Opening Speed
|
m/s
|
≤ 3
|
≤ 3
|
≤ 3
|
|||
|
Mechanical Life
|
Cycles
|
> 10000
|
> 10000
|
> 10000
|
|||
|
Other
|
Rated Filling Pressure (20°C)
|
MPa
|
0.05
|
0.07
|
0.1
|
||
|
SF₆ Gas Annual Leakage Rate
|
%/year
|
< 0.1
|
|||||
Application Scenarios
With its fast operation, intelligent parameter collection, and comprehensive safety protection, the 12kV Fast Electric Load Switch is widely used in global 12kV medium-voltage power distribution systems, especially suitable for: