Product Description
FZN21-40/T630-20 and FZN21-40(R)D/T125-31.5 type Indoor AC high voltage load switch- fuse combination units appliances for three-phase AC 40kV, 50Hz power system, or with the complete power distribution equipment and loop-network switch cabinet, combined substation and other ancillary uses, is widely used in urban network construction and transformation engineering, industrial and mining enterprises, high-rise buildings and public facilities, can be used as ring power supply unit or terminal equipment, play power distribution, control and protection.
Breaking with rated current, overload current (FZRN21-40D/T125-31.5 can short-circuit breaking current) and to prevent equipment missing running ability to switch a visible fracture of isolation, with combined installed capacity of the ground with the relevant switches and electrical spring agencies, to remote control.
The use of environmental conditions
- Air temperature: -25°C ~ +40°C;
- Altitude: ≤1000m;
- Relative humidity: daily average is not more than 95%,
- Installation places: No fire, explosion hazard, serious filthy places.
- Contamination level: II
Mainly technical parameters
| NO. |
Items |
Unit |
Value |
| 1 |
Rated voltage |
kV |
40.5 |
| 2 |
Rated frequency |
Hz |
50 |
| 3 |
Maximum rated current of fuse |
A |
63 |
| 4 |
1min power frequency withstand voltage |
kV |
95/110 |
| 5 |
Lightning impulse withstand voltage |
kV |
185/215 |
| 6 |
Rated peak withstand current |
kA |
50 |
| 7 |
4S rated short time withstand current |
kA |
20 |
| 8 |
Rated active load breaking current |
A |
1250 |
| 9 |
Rated closed loop breaking current |
A |
1250 |
| 10 |
Rated cable charging breaking current |
kA |
21 |
| 11 |
Rated short circuit breaking current |
kA |
31.5 |
| 12 |
Rated short circuit making current |
kA |
80(expected peak value) |
| 13 |
Mechanical life |
times |
10000 |