Outdoor Medium Voltage Air Load Break Switch-18-33kV

  • Outdoor Medium Voltage Air Load Break Switch-18-33kV
  • Outdoor Medium Voltage Air Load Break Switch-18-33kV
Key attributes
Brand ROCKWILL
Model NO. Outdoor Medium Voltage Air Load Break Switch-18-33kV
Rated voltage 40.5kV
Rated frequency 50Hz
Series FKW18
Product descriptions from the supplier
Description

Product Introduction

High voltage load air load break switch is a new type of load switch designed and manufactured by integrating domestic production experience of similar switches and foreign advanced technology. The outdoor load break switch is composed of isolation knife, arc extinguishing chamber and operating mechanism. Adopting the principle of gas gen eration and arc extinguishing, it has the advantages of simple structure, low maintenance workload, strong arc extinguishing ability, high fracture insulation level and high reliability, reaching the advanced level of similar products at home and abroad. FKW18 series outdoor AC high voltage load switch is suitable for outdoor three-phase AC power distribution system with rated voltage of 140.5KV and rated frequency of 50Hz. It can open and close distribution lines with load, and can also be used as open and close no-load lines. The use of no -load transformer, in the opening position, can meet the safety distance requirements specified for the disconnecting switch.

Working Environment

  • Altitude: no more than 3000m;
  • Ambient air temperature: the upper limit is 40°C, the lower limit is -25°C, and the daily temperature difference does not exceed 32K;
  • The wind pressure does not exceed 700Pa (equivalent to wind speed 34m/s);
  • Air pollution degree: Allowed to be level IV;
  • The earthquake intensity does not exceed 8 degrees;
  • The thickness of icing shall not exceed 10mm

Main Technical Parameters

 No ltem Unit Dala
1 Rated voltage kV 40.5
2 Rated current A 800
3 Raled frequency Hz 50
4 Rated peak withstand current kA 50
5  Rated short-time withstand current  kA 20
6 Rated short-time withstand current duration S 4
7 Rated aclive load breaking current A 800
8 Rated closed-loop breaking current A 800
9 Rated cable charging current A 10
10 Rated active load breaking current A 31.5
11 No-load transformer current opening rated capacity kVA 1250
12 Rated short circuit switching current kA 50
13 Main circuit resistance μΩ ≤95
14 1 min Power frequency
withstand voltage (valid value
Dry Interphase,phase to earth kV 95
isolating fracture 15
Wet Interphase,phase to earth kV 85
15 Lightning impulse withstand voltage (peak) Interphase,phase to earth kV 185
isolating fracture 215
16 Mechanical life Times 2000
17 Different Periods of Three-phase Separation and Closing ms ≤15
18 Motor voltage,power  V  W 220 ≤200
19 Deflection of blade rigid position mm ≤5
20 Main contact blade pressure N 420±42
21 Contact blade opening distance mm ≥360
22 Rated operating torque  N·m ≤300
Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO