| Brand | ROCKWILL |
| Model NO. | The new SF6 free air insulated switchgear |
| Rated voltage | 24kV |
| Rated frequency | 50Hz |
| Series | JesAir |
Product Description
JesAir is the new, completely SF6-free medium voltage switchgear that combines reliability, safety, and sustainability. Designed to meet the requirements of EU Regulation 2024/573, the switchgear eliminates the use of fluorinated greenhouse gases, offering an environmentally friendly alternative that complies with European standards.
Electrical and construction characteristics
| Rated Voltage | Ur [kV] | 24 |
| Rated Frequency | Fr [Hz] | 50 |
| Rated Power Frequency Withstand Voltageat 50Hz | Ud [kV] | 50 |
| Rated lightning impulse withstand vlt (1.2/50 µs) | Up [kV] | 125 |
| Rated thermal current of main busbars | Ir [A] | 630/800 |
| Rated short-time withstand current | Ik [kA/s] | 16/1 or 20/1 |
| Internal arc classification | IAC | Optional |
| Type of accessability | AFLR | Optional |
| Arc fault current / Duration | Ia [kA/s] | 16/1 or 20/1 |
| External degree of protection | IP | IP3X Escluse sedi di manovra |
| Internal degree of protection | IP | IP2X |
| Mechanical impact resistance | IK | 10 |
| AC auxiliary supply voltage | Vaux [V] | 220Vca |
| DC auxiliary supply voltage | Vaux [V] | 110Vcc |
| Minimum operating temperature | [°C] | -5 |
| Maximum operating temperature | [°C] | 40 |
| Paint color point | – | RAL 7035 |
Main features of the JesAir switchgear
Fields of application
The JesAir range of switchgears is used in secondary medium voltage electrical distribution and can be easily installed in transformer cabins to manage and protect power lines, measuring equipment, and transformers.
Standard references
The equipment complies with the following standards:
In particular, JESAIR switchgears can be classified as:
Internal arc: IAC AFLR (on request only)