Solid Sealed Load Switch-40.5kV

  • Solid Sealed Load Switch-40.5kV
Nyckelattribut
Varumärke ROCKWILL
Modellnummer Solid Sealed Load Switch-40.5kV
Nominell spänning 40.5kV
Nominell ström 630A
Nominell frekvens 50Hz
Serier RMR
Leverantörens produktdeskrifter
Beskrivning
Product Overview
RMR-40.5 series indoor AC high-voltage vacuum load switch and load switch-fuse combination unit (hereinafter referred to as the series solid-sealed vacuum load switch) are independently designed and developed by our company in accordance with GB3804、GB16926 and IEC 62271.They are suitable for AC 50 Hz, rated voltage 40.5 kV systems, specially designed for 35 kV wind power and solar power systems.They can be used as independent electrical units in 40.5 kV power systems or box-type substations.The product features a reasonable structure and adopts the CTE3 two-stage transmission spring operating mechanism, which is independently developed by our company and has won the national invention patent, ensuring simple and reliable operation.
Model Explanation
Indoor AC High-Voltage Vacuum Load Switch
Solid Sealed Load Switch-40.5kV
Indoor AC High-Voltage Vacuum Load Switch-Fuse Combination Unit
Solid Sealed Load Switch-40.5kV

Operating Environment Conditions

  • Ambient temperature: -25℃ to +40℃;
  • Relative humidity: daily average ≤ 95%, monthly average ≤ 90%;
  • The ambient air is free from significant contamination by dust, smoke, corrosive or flammable gases, vapors, or salt spray;
  • No fire or explosion hazards at the installation site;
  • Seismic intensity ≤ 8 degrees; installation site with an inclination ≤ 5°.
Note: The above are the conventional operating conditions specified in GB/T 11022. For special environments such as high altitude, heavy salt spray, or extreme cold/heat, the technical design can be modified for custom manufacturing based on the above requirements.
Switch Performance Parameters
 
No. Item Unit RMR(EP)-40.5 Vacuum Load Switch RMR(EP)-40.5 Load Switch-Fuse Combination Equipment
1 Rated Voltage kV 40.5 40.5
2 Rated Frequency Hz 50 50
3 Rated Current A 630; 1250 Fuse rated current: 100; 125 (max. rated current of fuse)
4 Rated Short-Circuit Breaking Current of Fuse kA - 31.5; 40; 50
5 Rated Active Load Breaking Current A 630; 1250 -
6 Rated Transformer Charging Breaking Current A 63; 125 -
7 Rated Closed-Loop Breaking Current A 630; 1250 -
8 Rated Cable Charging Breaking Current A 21 -
9 Rated Line Charging Breaking Current A 2.1 -
10 Rated Earth Fault Breaking Current A 100 -
11 Rated Peak Short-Circuit Making Current kA 63 -
12 Rated Peak Withstand Current kA 63 -
13 Rated Short-Time Withstand Current kA/s
 Load Switch (including disconnector): 20/4, 25/4
 Earthing Switch: 2/2, 25/4
-
14 Rated Transfer (Make-Break) Current A - 2000
15 1min Power Frequency Withstand Voltage (RMS), Phase-to-Phase / Phase-to-Ground kV/kV 95/118 95/118
16 Lightning Impulse Withstand Voltage (Peak), Phase-to-Phase / Phase-to-Ground kV/kV 185/215 185/215
17 Main Circuit Resistance μΩ 180 (excluding fuse) 180 (excluding fuse)
18 Mechanical Life Cycles 10,000 10,000
19 Contact Opening Distance mm 17±1 17±1
20 Contact Wear Allowance mm 3 3
21 Average Opening Speed m/s 1.0–1.6 1.0–1.6
22 Average Closing Speed m/s 0.6–1.2 0.6–1.2
23 Three-Phase Opening/Closing Asynchronism ms ≤2 2
24 Contact Bounce Time (Closing) ms 5 ≤5
25 Pole Center Distance mm 440/470/500 440/470/500
26 Operating Torque of Vacuum Interrupter (Closing) N·m ≤90 90
27 Operating Force of Vacuum Interrupter (Opening) N 10 ≤10

Outline Drawing

RMR(EP)-40.5D/T100-31.5
Enclosed Indoor High-Voltage AC Vacuum Load Switch – Fuse Combination Equipment
Front View, Left-Side Operation

 

 

Solid Sealed Load Switch-40.5kV

Solid Sealed Load Switch-40.5kV

Outline Drawing

RMR(EP)-40.5D/T100-31.5 (Flat Installation)
Enclosed Indoor High-Voltage AC Vacuum Load Switch – Fuse Combination Equipment
Front View, Left-Side Operation

Solid Sealed Load Switch-40.5kV

Solid Sealed Load Switch-40.5kV

Switchgear Arrangement Diagram
RMR(EP)-40.5D/T100-31.5
(Width: 950+1050 mm × Depth: 1800 mm × Height: 2300 mm)
Indoor Enclosed High-Voltage AC Vacuum Load Switch – Fuse Combination Equipment (Phase-to-Phase Distance: 440 mm)

Solid Sealed Load Switch-40.5kV

Skicka förfrågan
+86
Klicka för att ladda upp fil
Ladda ner
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Ladda ner
Hämta IEE-Business applikationen
Använd IEE-Business-appen för att hitta utrustning få lösningar koppla upp med experter och delta i branssammarbete när som helst var som helst fullt ut stödande utvecklingen av dina elprojekt och affärsverksamhet
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO