| Varumärke | ROCKWILL |
| Modellnummer | Solid Sealed Load Switch-40.5kV |
| Nominell spänning | 40.5kV |
| Nominell ström | 630A |
| Nominell frekvens | 50Hz |
| Serier | RMR |


Operating Environment Conditions
| No. | Item | Unit | RMR(EP)-40.5 Vacuum Load Switch | RMR(EP)-40.5 Load Switch-Fuse Combination Equipment |
|---|---|---|---|---|
| 1 | Rated Voltage | kV | 40.5 | 40.5 |
| 2 | Rated Frequency | Hz | 50 | 50 |
| 3 | Rated Current | A | 630; 1250 | Fuse rated current: 100; 125 (max. rated current of fuse) |
| 4 | Rated Short-Circuit Breaking Current of Fuse | kA | - | 31.5; 40; 50 |
| 5 | Rated Active Load Breaking Current | A | 630; 1250 | - |
| 6 | Rated Transformer Charging Breaking Current | A | 63; 125 | - |
| 7 | Rated Closed-Loop Breaking Current | A | 630; 1250 | - |
| 8 | Rated Cable Charging Breaking Current | A | 21 | - |
| 9 | Rated Line Charging Breaking Current | A | 2.1 | - |
| 10 | Rated Earth Fault Breaking Current | A | 100 | - |
| 11 | Rated Peak Short-Circuit Making Current | kA | 63 | - |
| 12 | Rated Peak Withstand Current | kA | 63 | - |
| 13 | Rated Short-Time Withstand Current | kA/s | • Load Switch (including disconnector): 20/4, 25/4 • Earthing Switch: 2/2, 25/4 |
- |
| 14 | Rated Transfer (Make-Break) Current | A | - | 2000 |
| 15 | 1min Power Frequency Withstand Voltage (RMS), Phase-to-Phase / Phase-to-Ground | kV/kV | 95/118 | 95/118 |
| 16 | Lightning Impulse Withstand Voltage (Peak), Phase-to-Phase / Phase-to-Ground | kV/kV | 185/215 | 185/215 |
| 17 | Main Circuit Resistance | μΩ | ≤180 (excluding fuse) | ≤180 (excluding fuse) |
| 18 | Mechanical Life | Cycles | 10,000 | 10,000 |
| 19 | Contact Opening Distance | mm | 17±1 | 17±1 |
| 20 | Contact Wear Allowance | mm | 3 | 3 |
| 21 | Average Opening Speed | m/s | 1.0–1.6 | 1.0–1.6 |
| 22 | Average Closing Speed | m/s | 0.6–1.2 | 0.6–1.2 |
| 23 | Three-Phase Opening/Closing Asynchronism | ms | ≤2 | ≤2 |
| 24 | Contact Bounce Time (Closing) | ms | ≤5 | ≤5 |
| 25 | Pole Center Distance | mm | 440/470/500 | 440/470/500 |
| 26 | Operating Torque of Vacuum Interrupter (Closing) | N·m | ≤90 | ≤90 |
| 27 | Operating Force of Vacuum Interrupter (Opening) | N | ≤10 | ≤10 |
Outline Drawing
RMR(EP)-40.5D/T100-31.5
Enclosed Indoor High-Voltage AC Vacuum Load Switch – Fuse Combination Equipment
Front View, Left-Side Operation


Outline Drawing
RMR(EP)-40.5D/T100-31.5 (Flat Installation)
Enclosed Indoor High-Voltage AC Vacuum Load Switch – Fuse Combination Equipment
Front View, Left-Side Operation


Switchgear Arrangement Diagram
RMR(EP)-40.5D/T100-31.5
(Width: 950+1050 mm × Depth: 1800 mm × Height: 2300 mm)
Indoor Enclosed High-Voltage AC Vacuum Load Switch – Fuse Combination Equipment (Phase-to-Phase Distance: 440 mm)