Key attributes
Brand ROCKWILL
Model NO. Customization of Dead tank SF6 Gas Circuit-Breaker
Rated voltage 220kV
Rated normal current 5000A
Rated frequency 50/60Hz
Series RHD
Product descriptions from the supplier
Description

Product Overview

The RHD Series Dead-Tank SF6 Circuit Breaker is engineered for 'customized high-voltage power system solutions', covering standard voltage grades from RHD-40.5 to RHD-550 and supporting 'non-standard voltage customization' to precisely match your unique grid upgrade or construction needs. As a dead-tank type, its grounded tank isolates high-voltage components, ensuring superior insulation performance and safety—making it the go-to choose for demanding high-voltage scenarios.

About customization

We offer full customization services for voltage classes, including single-phase, two-phase, and three-phase configurations, as well as non-standard voltage/current solutions. Examples of available voltage and current specifications include 1250 A 75 kV, 3200 A 46 kV, 60 kV, 69 kV, and 75 kV (we support customization ranging from 10 kV to 800 kV for voltage and 1250 A to 6300 A for current). Regardless of your power grid's voltage specifications, we tailor the circuit breaker for seamless integration.

All products are fully assembled and tested at our factory before being shipped directly to your site—no disassembly of key components is required. This eliminates the need for on-site high-voltage testing, significantly saving you time and costs.

Key features

 1. Superior Seismic Resistance

Adopting a low-center-of-gravity design, the breaker can withstand an earthquake intensity of up to 9 degrees, ensuring stable performance in seismic-prone areas—consistent with the RHD series’ proven anti-seismic capability.

2. Excellent Arc-Extinguishing Performance & Long Service Life

Leveraging the high arc-extinguishing efficiency of SF6 gas, the breaker achieves a rated short-circuit breaking current of ≥50kA. It boasts an electrical life of more than 20 operations and a mechanical life of up to 10,000 cycles, significantly reducing equipment replacement and maintenance costs.

3. Low SF6 Gas Leakage Rate

The hermetic metal tank structure minimizes SF6 gas leakage, with an annual leakage rate of ≤1%—far below industry averages. This design not only avoids safety hazards from gas leakage but also reduces environmental impact. 

4. Modular Design & Flexible Expansion

It supports on-demand configuration of built-in current transformers (CTs), with up to 15 CTs available for measurement or protection purposes. The standardized module interface allows flexible combination to meet diverse substation design and layout requirements, especially suitable for space-constrained scenarios.

5. Strong Environmental Adaptability

The breaker operates stably in extreme conditions: ambient temperature ranging from -40℃ to +55℃, maximum daily temperature difference of 32K, altitude up to 3,000m, and air pollution level up to Class IV. It also resists wind pressure of 700Pa (equivalent to 34m/s wind speed) and icing thickness of up to 20mm.

6. Comprehensive Safety Protection

Equipped with anti-mis operation interlocking devices, it effectively prevents accidents caused by incorrect operations. Before delivery, the breaker undergoes lightning impulse tests to eliminate insulation discharge risks from production and assembly, ensuring reliable quality.

7. Maintenance-Free Operating Mechanism

It adopts a spring-operated mechanism that is oil-free, gas-free, and maintenance-free. This mechanism delivers stable performance, low noise, and high reliability, reducing long-term operational workload.

    Technology Parameters

    Item Unit Parameters
    customization of Rated Voltage kV

    11kV/12kV/13.8kV/15kV/22kV/33kV/44kV/60kV/63kV/66kV/69kV/88kV/115kV/123kV/125kV/126kV/132kV/138kV/145kV/150kV/170kV/220kV/225kV/230kV/245kV/275kV/330kV/345kV/400kV/765kV/800kV

    customization of Rated  current A 1250 to 6300
    Rated frequency Hz 50/60
    1min Power frequency withstand voltage kV Max to 750
    Lightning impulse withstand voltage kV Max to 1675
    First open pole factor   1.5/1.3/1.55
    Rated short circuit breaking current kA 16 to 63
    Rated short - circuit duration s 4,3
    Rated out - of - phase breaking current   10
    Rated cable charging current   10/50/125
    Rated peak value withstand current kA 80/100/125
    Rated making current (peak) kA 80/100/125
    Creepage distance mm/kV 25 - 31
    SF6 gas leakage rate (per year)   ≤1%
    Rated SF6 gas pressure(20℃ gauge pressure) Mpa 0.5/0.4,0.5,0.6
    Alarm/blocking pressure(20℃ gauge pressure) Mpa 0.45/0.4,0.35/0.33,0.45/0.40,0.55/0.50
    SF6 annual gas leakage rate   ≤0.5
    Gas moisture content Ppm(v) ≤150
    Heater voltage   AC220/DC220
    Voltage of control circuit DC DC110/DC220/DC230
    Voltage of energy - store motor V DC 220/DC 110/AC 220/DC230
    Applied standards   GB/T 1984/IEC 62271 - 100

     

    Name unit Parameters
    Opening time ms 27±3
    Closing time ms 90±9
    Minute and conjunction time ms 300
    Together--ivide the time ms ≤60
    Simultaneity of opening ms ≤3
    Closing simultaneity ms ≤5
    Moving contact stroke mm 150+2-4
    Contact contact stroke mm 27±4
    Opening speed m/s 4.5±0.5
    Closing speed m/s 2.5±0.4
    Mechanical life times 6000
    Operation sequence   O - 0.3s - CO - 180s - CO
    Note: The opening and closing speed and time are the characteristic values of the circuitbreaker when it is single divided and closed under rated conditions. The closing speed is theaverage speed of the moving contact from the rigid closing point to 10 ms before closing, andthe opening speed is the average speed of the moving contact within 10 ms from the justequinox to 10 ms after the separation.

    Application Scenarios

    1. Large Hub Substations

    Ideal for 220kV+ key hub substations, the customized RHD breaker controls and protects main power circuits. Its non-standard voltage adaptability ensures seamless integration into existing or upgraded grid architecture.

    1. New Energy Grid-Connection Systems

    Suitable for high-voltage grid connections in wind and solar power bases. Custom voltage ratings ensure reliable integration of renewable energy into the main grid, even in projects with unique voltage requirements.

    1. Industrial High-Voltage Power Systems

    Perfect for heavy industries (metallurgy, chemicals) with specialized voltage needs. The breaker’s robust performance and customizability guarantee stable power supply for high-power industrial equipment.

     

     

     

    Documentation Resource Library
    RHD-Dead Tank SF6 Circuit Breaker Catalog
    Restricted.
    RHD-Dead Tank SF6 Circuit Breaker Catalog
    Catalogue
    English
    Consulting
    Consulting
    FAQ
    Q: How to choose the voltage level of high-voltage sulfur hexafluoride circuit breaker?
    A:

    1. Select the circuit breaker corresponding to the voltage level based on the power grid level
    The standard voltage (12/24/40.5/72.5/126/170/245/363/420/550/800/1100kV) is matched with the corresponding nominal voltage of the power grid. For example, for a 35kV power grid, a 40.5kV circuit breaker is selected. According to standards such as GB/T 1984/IEC 62271-100, the rated voltage is ensured to be ≥ the maximum operating voltage of the power grid.
    2. Applicable scenarios for non-standard customized voltage
    Non standard customized voltage (11/22/44/52/132/230/275/300/345/400/380/765kV) is used for special power grids, such as the renovation of old power grids and specific industrial power scenarios. Due to the lack of suitable standard voltage, manufacturers need to customize according to power grid parameters, and after customization, insulation and arc extinguishing performance must be verified.
    3. The consequences of selecting the wrong voltage level
    Choosing a low voltage level can cause insulation breakdown, leading to SF leakage and equipment damage; Choosing a high voltage level significantly increases costs, increases operational difficulties, and may also result in performance mismatch issues.

    Q: What are the structural characteristics of the tank circuit breaker?
    A:

    Integral Tank Structure:

    • Integral Tank Structure: The breaker's arc quenching chamber, insulating medium, and related components are sealed within a metal tank filled with an insulating gas (such as sulfur hexafluoride) or insulating oil. This forms a relatively independent and sealed space, effectively preventing external environmental factors from affecting the internal components. This design enhances the insulation performance and reliability of the equipment, making it suitable for various harsh outdoor environments.

    Arc Quenching Chamber Layout:

    • Arc Quenching Chamber Layout: The arc quenching chamber is typically installed inside the tank. Its structure is designed to be compact, enabling efficient arc quenching within a limited space. Depending on different arc quenching principles and technologies, the specific construction of the arc quenching chamber may vary, but generally includes key components such as contacts, nozzles, and insulating materials. These components work together to ensure that the arc is quickly and effectively extinguished when the breaker interrupts the current.

    Operating Mechanism:

    • Operating Mechanism: Common operating mechanisms include spring-operated mechanisms and hydraulic-operated mechanisms.

    • Spring-Operated Mechanism: This type of mechanism is simple in structure, highly reliable, and easy to maintain. It drives the opening and closing operations of the breaker through the energy storage and release of springs.

    • Hydraulic-Operated Mechanism: This mechanism offers advantages such as high output power and smooth operation, making it suitable for high-voltage and high-current class breakers.

    Q: What Non-standard voltage level customization services can be provided for this tank-type circuit breaker?
    A:
    We provide customized services for the following voltage levels, including but not limited to11kV/12kV/13.8kV/15kV/22kV/33kV/44kV/60kV/63kV/66kV/69kV/88kV/
    115kV/123kV/125kV/126kV/132kV/138kV/145kV/150kV/170kV/220kV/225kV/230kV/
    245kV/275kV/330kV/345kV/400kV/756kV/800kV
     
     
     
    Related Products
    Related Solutions
    Inquiry
    Download
    Experts Electrical is dedicated to serving the personnel in the global power industry.
    Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
    App Store
    Download
    Get the IEE Business Application
    Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
    IEE Business
    Source professional electrical partners, experts, and explore smart grid & energy solutions.