Highly Adaptable Outdoor HV Ring Main Unit - 6kV

  • Highly Adaptable Outdoor HV Ring Main Unit - 6kV
Key attributes
Brand ROCKWILL
Model NO. Highly Adaptable Outdoor HV Ring Main Unit - 6kV
Rated voltage 7.6kV
Rated normal current 630A
Rated frequency 50Hz
Series RMR
Product descriptions from the supplier
Description

6kV outdoor HV Ring Main Unit Description

It is a complete power distribution assembly suitable for 3.6~24kV, three-phase AC 50Hz, single bus sectionalized systems.It is mainly used for power transmission of small and medium-sized generators in power plants, power receiving and transmission in distribution systems and substations of industrial and mining enterprises, and starting of large high-voltage motors, so as to control, protect and monitor the power system.

The switchgear complies with IEC298 and GB3906-91 standards.In addition to the domestic VS1 vacuum circuit breaker, it can also be equipped with ABB VD4, Siemens 3AH5, domestic ZN65A, GE VB2 and other circuit breakers. It is an excellent performance power distribution equipment.

Product Advantages

  • The structure of the 12kV Switchgear Panel is bolt by aluminum zinc alloy board after the process of CNC machine tool and multi bending technology;
  • All the operation can be done after the Switchgear Panel door is closed;
  • High protection degree, protect the intruder of sundries and pests;
  • Simple and effective “five-prevention” lock function, protect error operation;
  • Can adopt VS1 and CD4 vacuum circuit breaker;
  • Easy replacement of the circuit breaker and free exchange of the drawers;
  • The Switchgear Panel can be installed by the wall, maintenance in the front, which reduces the floor space;
  • Large space of the cable room can connect many cables;
  • The relay room and the cable room can respectively add a heater to avoid freezing or erosion.

Service environment

a. The ambient air temperature : -5°C ~ +40°C;
b. Daily average temperature(Within 24h): ≤+35℃
c. Altitude:≤1000m;
d. Relative humidity: within 24h, daily average value ≤ 95% , daily average vapor pressure≤ 2.2KPa;
monthly average value ≤ 90%, monthly average vapor pressure≤ 1.8KPa
* Ambient air is not significantly polluted by dust, smoke, corrosive and / or flammable gas, vapor or salt contamination
Main technical parameters

Rated voltage

.....................................

kV

3.6、7.2、12

Rated frequency

.....................................

Hz

50

Rated current of circuit breaker

.....................................

A

630/4000

Rated current of switchgear

.....................................

A

630/4000

Rated short-time withstand current (4S)

.....................................

kA

20、25、31.5、40

Rated peak withstand current (peak)

.....................................

kA

50、63、80、100

Rated short-circuit breaking current

.....................................

kA

20、25、31.5、40

Rated insulation level 1min power frequency withstand voltage

Pole-to-pole, pole-to- ground

kV

24、32、42

Between open contacts

kV

24、32、48

Lightning impulse withstand voltage (peak)

Pole-to-pole, pole-to- ground

kV

40、60、75

Between open contacts

kV

46、70、85

The shell is IP4X, and it is IP2X when the compartment door and circuit breaker chamber door are opened

Product Line

Highly Adaptable Outdoor HV Ring Main Unit - 6kV

Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Email
E-mail
WhatsApp
WhatsApp
Chat