Medium voltage Pole Mounted Drop Out Automatic Sectionalizer 15kV 27kV 38 kV

  • Medium voltage Pole Mounted Drop Out Automatic Sectionalizer 15kV 27kV 38 kV
Key attributes
Brand ROCKWILL
Model NO. Medium voltage Pole Mounted Drop Out Automatic Sectionalizer 15kV 27kV 38 kV
Rated voltage 38kV
Rated frequency 50/60Hz
Rated capacity 200kVA
Series RDK
Product descriptions from the supplier
Description

The ROCKWILL AutoLink Sectionalizer serves as a dedicated isolating component designed to automatically disconnect faulty segments of overhead power networks in the event of a permanent fault. In cases of temporary faults, the AutoLink sectionalizer enables upstream reclosers or breakers to resolve the issue without disrupting the entire circuit. Available in both electronic and wireless configurations, the AutoLink family is engineered to enhance power supply reliability and ensure uninterrupted service continuity for overhead distribution systems.

Product Overview

Designed for three-phase AC power systems operating at 50Hz with a rated voltage range of 10-40.5kV, the AutoLink sectionalizer is installed on overhead distribution lines to isolate faults when paired with reclosers or circuit breakers. When a fault occurs on the line and the fault current meets or exceeds the preset threshold, the sectionalizer records the number of tripping operations performed by the upstream recloser. Once this count reaches the preconfigured limit, the sectionalizer automatically trips to disconnect the faulty segment.

The AutoLink sectionalizer will initiate an automatic trip only when all three of the following conditions are met simultaneously:

  • The fault current exceeds the preset pickup current value;
  • The recorded number of upstream recloser trips reaches the user-configured count (1, 2, 3, or 4);
  • The circuit experiences a voltage loss and the current drops below 300mA.

If any of these conditions are not satisfied, the sectionalizer will not trigger an automatic trip. Equipped with a microcomputer and an integrated operating trip mechanism, this device operates without the need for external auxiliary power, ensuring reliable performance even in remote or inaccessible installation locations.

Key Benefits

  • Boosts power supply reliability and service continuity by effectively distinguishing between temporary and permanent network faults
  • Minimizes inventory requirements with a universal design that accommodates all current ratings, eliminating the need for multiple sizes
  • Facilitates hassle-free, rapid installation that does not require specialized tools or complex on-site setup
  • Cuts down maintenance time significantly, thanks to its field-configurable settings and easy reset functionality
  • Lowers overall operational expenses by reducing downtime, maintenance labor, and inventory costs

Key Features

  • Available in three standard voltage ratings: 15 kV, 27 kV, and 38 kV, covering a wide range of overhead network requirements
  • Allows users to adjust both nominal current and fault count settings according to specific project or network needs
  • Operates independently without the need for an external power source, enhancing installation flexibility and reliability
  • Comprehensive product family: includes single-phase, loadbreak, mechanical three-phase, and wireless three-phase models to suit diverse application scenarios
  • Functions independently of time-current curves, ensuring consistent performance regardless of upstream protection settings

Technical data

S/N Name Unit RDK10-12/D315 RDK10-12/D200 RDK□-40.5/D200
1 Rated voltage KV 12 12 40.5
2 Rated current A 200 200 200
3 Rated frequency Hz 50 50 50
4 Pickup current rating A 8~400A 8~400A 8~400A
5 Short time withstand current(RMS) KA 10 10 10
6 Short circuit withstandtime s 1 1 1
7 Short time withstand current (PEAK) KA 16 20 20
8 Counting time time 1, 2, 3, 4 1, 2, 3, 4 1, 2, 3, 4
9 Max memory time S 20 20 20
10 Max reset time S 20 20 20
11 Permissible deviation of pick up current for memory rest time % ±10 ±10 ±10
12 Opening time ms ≤200 ≤200 ≤200
13 Main circuit resistance μ Ω ≤400 ≤400 ≤400
14 Mechanic life Time 500 500 500
15 Horizontal pulling force of terminal N 250 250 250
16 Manual open moment N·m —— —— ——
17 Manual open force N ≤120 ≤120 ≤120
18 BIL(phase to ground) KV 110 185 185
19 BIL(between gap) KV 110 220 22
20 PFWV(phase to ground) dry  
 
KV
 
55 95 95
wet 45 80 80
21 PFWV(between gap) dry  
 
KV
 
55 110 110
wet 45 95 95
22 PFWV of control circuit KV 2 2 2
23 Dirty proof grade Class
24 Ice proof thickness mm ≤7 ≤1 ≤1
25 Pickup current (four classes) and Counting time can be set   —— YES YES
26 Mechanical interlocking for 3 phase devices and automatic reset   —— YES YES

12/24kV IEC/ANSI

Medium voltage Pole Mounted Drop Out Automatic Sectionalizer 15kV 27kV 38 kV

36/38kV IEC/ANSI

Medium voltage Pole Mounted Drop Out Automatic Sectionalizer 15kV 27kV 38 kV

Installation

Medium voltage Pole Mounted Drop Out Automatic Sectionalizer 15kV 27kV 38 kV

Send inquiry
+86
Click to upload file
Download
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Download
Get the IEE Business Application
Use the IEE-Business app to find equipment, obtain solutions, connect with experts, and participate in industry collaboration anytime, anywhere—fully supporting the development of your power projects and business.
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO