| Varumärke | ROCKWILL |
| Modellnummer | 20kV-630A Outdoor Air/Sf6 Gas Insulation Ring Main Unit |
| Nominell spänning | 24kV |
| Nominell ström | 630A |
| Nominell frekvens | 50/60Hz |
| Serier | RMR |
Description
The complete variety, novel design, and excellent quality of our 3 phase dry power transformer, high voltage electrical switchgear, electrical distribution transformer have impressed our customers both at home and abroad. Insisting on the high quality generation line management and customers expert assistance, we now have designed our resolution to offer our buyers using the to start with amount getting and just after services practical experience. We are well aware that quality and service are the foundation of a company's survival, thus we will continue to uphold customer first and pursue excellence. They are sturdy modeling and promoting effectively all over the world.
Outdoor SF6 Ring Main Unit
RMR is the ring main unit for the asecondary distribution network. RMR can provide 10 different configurations, suitable for most switching applications in 12/24 kV distribution networks. It is scalable and combined with ABB's flexible modular and compact switchgear SafePlus concept, it is a complete solution for 12/24 kV secondary distribution networks. RMR and SafePlus have the same user interface. RMR is a completely sealed system with a stainless steel tank containing all live parts and switching functions. Sealed steel tanks with constant atmospheric conditions ensure a high degree of reliability as well as personnel safety and almost maintenance-free systems. The RMR concept provides a choice of switch fuse combinations or circuit breakers with relays to protect the transformer. RMR can provide an integrated remote control and monitoring unit. This product complies with the standards of IEC60420, GB/T11022, GB3804, GB3906
Outdoor SF6 ring main unit use environment:
a) Air temperature: highest temperature: +40℃; lowest temperature: -20℃
b) Humidity: monthly average humidity 95%; daily average humidity 90%.
c) Altitude: Maximum installation height: 2500m
d) Obviously there is no ambient air polluted by corrosive and combustible gases, steam, etc.
Technical data
|
No. |
Item |
Unit |
C Module |
V Module |
||
|
Load break switch |
Circuit breaker |
|||||
|
1 |
Rated voltage |
kV |
12 |
24 |
12 |
24 |
|
2 |
Rated current |
A |
630 |
|||
|
3 |
Rated frequency |
Hz |
50/60 |
|||
|
4 |
1min Power frequency withstand voltage |
kV |
45 |
55 |
45 |
55 |
|
5 |
Lightning impulse withstand voltage |
kV |
75 |
125/150 |
75 |
125/150 |
|
6 |
Rated transfer current |
A |
1700 |
1400 |
||
|
7 |
Rated active load and close circuit breaking current |
A |
630 |
|||
|
8 |
Rated cable charge breaking current |
A |
50&10 |
|||
|
9 |
Rated short circuit breaking current |
kA |
20 |
16 |
||
|
10 |
Rated short circuit making current(peak) |
kA |
63 |
50 |
63 |
50 |
|
11 |
Short time (2s) withstand current, load switch/earth |
kA |
25/20 |
20/20 |
25/20 |
20/20 |
|
12 |
Rated withstand current (peak) |
kA |
63 |
50 |
63 |
50 |
|
13 |
Mechanism life |
Times |
3000 |
10000 |
3000 |
|
|
14 |
Dimension ( per unit) |
mm |
370x750x1345 |
|||
Product Photos