Main Technical Parameters

Rated voltage 12kV/24kV
Rated current 630/1250A
Rated frequency 50Hz
Rated short-term power frequencywithstand voltage dry test 48kV Between phases, phase to earth 42kV,Acrossthe interrupter,across isolatingdistance:48 kV
Rated lightning impulse with stand voltage 85 kV Between phases, phase to earth 75 kVA cross the interrupter, across isolatingdistance:85 kV
Short-time withstand current 25kA
Duration of short-circuit 4S
Peak withstand current 63kA
Short-circuit making current 63kA
Short-circuit breaking current  
AC component 25kA
DC component 51%
DC time constant 45 ms
Mechanical endurance Circuit-breaker:10000 times, Class M2. Disconnector: 3000times. class Ml: Earthing position: 3000 times, ClassM1

Use Of Condition

  • Ambient air temperature: from -5ºC to +40ºC, and average temperature shall be not higher than +35ºC in 24h.
  • Atmospheric conditions, relative humidity shall not be over 50% when the highest temperature is at +40ºC. Bu higher humidity is allowed when the temperature is lower, for instance, humidity can be 90% when +20ºC. It shall be taker into consideration that changes in temperature can accidentally cause condensation.
  • Absolute elevation shall be not higher than 2000m. (Otherwise, the capacity shall be reduced)
  • The temperatures for transportation and storage of this device is from +25ºC to +55ºCC, in a short time (no longer than 24h) the limiting temperature can reach +70ºC, in that case, unrecoverable damages will not occur on the device In case the above service conditions are not satisfied. the user shall consult with the manufacturer
  • If this device is used in offshore oil platforms or nuclear stations, another technical agreement shall be signed.

Product Size

Solid Insulation Lbs Load Break Switch with Vacuum Interrupter 12/24kV 630A

Site Working Photos

Solid Insulation Lbs Load Break Switch with Vacuum Interrupter 12/24kV 630A

Запит
+86
Натисніть, щоб завантажити файл
Завантажити
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Завантажити
Отримати додаток IEE Business
Використовуйте додаток IEE-Business для пошуку обладнання отримання рішень зв'язку з експертами та участі у галузевій співпраці в будь-якому місці та в будь-який час — повна підтримка розвитку ваших енергетичних проектів та бізнесу
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO