Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit

  • Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit
Attributi chiave
Marca ROCKWILL
Numero modello Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit
tensione nominale 12kV
corrente nominale 630A
Serie RMR
Descrizioni prodotto fornitore
Descrizione

Product Introduction

RMR‑12 Series Center‑mounted Sealed Pole Vacuum Load Break Switch‑Fuse Combination Apparatus is a new‑generation vacuum switching device developed based on unique design concepts and market demands.It is widely used in indoor armored air‑insulated switchgears.It complies with the standards including GB 3804‑2004 and GB 16926‑1997.Under normal conditions and within its technical parameters,it can operate safely and reliably in power systems of the corresponding voltage level.
Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit
Operating Environment
  • Ambient Temperature: Maximum +40°C, minimum -25°C.
  • Ambient Humidity: Daily average relative humidity ≤ 95%; monthly average relative humidity ≤ 90%.
  • Saturated Vapor Pressure: Daily average saturated vapor pressure ≤ 2.2×10⁻³ MPa; monthly average saturated vapor pressure ≤ 1.8×10⁻³ MPa.
  • Altitude: Not exceeding 1500 m.
  • Seismic Intensity: Not exceeding 8 degrees.
  • Application Site: No dripping water, no flammable or explosive hazards, no chemically corrosive gases, and no severe dust.
  • Special Note: If the product's operating environment exceeds the above specifications, users may negotiate with our company for confirmation.

Main Technical Parameters

No. Item Unit Parameter
1 Contact Opening Distance mm 8–10
2 Contact Pressure Spring Stroke mm 3–5
3 Phase-to-Phase Center Distance mm 150 / 210 / 275
4 Opening/Closing Asynchronism ms ≤ 2
5 Contact Bounce Time (Closing) ms ≤ 3
6 Average Closing Speed m/s 0.4–0.8
7 Average Opening Speed m/s 1.0–1.4
8 Closing Time (at Rated Operating Voltage) ms ≤ 60
9 Opening Time (at Rated Operating Voltage) ms ≤ 30
10 Main Circuit Resistance μΩ ≤ 250
11 Allowable Wear Thickness of Moving and Stationary Contacts mm 3

Technical Parameters

No. Item Unit RMR-12/T630-20 Vacuum Circuit Breaker RMR-12/T630-20 Vacuum Circuit Breaker – Fuse Combination Equipment
1 Rated Voltage kV 12 12
2 Power Frequency Withstand Voltage (Phase-to-Phase, Phase-to-Ground) kV 42 42
3 Lightning Impulse Withstand Voltage (Phase-to-Phase, Phase-to-Ground) kV 75 75
4 Rated Current A 630 160 (Fuse)
5 Rated Short-Circuit Breaking Current kA - 50 (Fuse)
6 Rated Short-Time Withstand Current kA 20 -
7 Rated Peak Withstand Current kA 50 -
8 Rated Closing Switching Current kA 50 -
9 Rated Cable Charging Breaking Current A 16 -
10 Rated Making Current A - 3150
11 Breaking Capacity of Transformer kVA 1600 -
12 Electrical Life Cycles 10,000 -
13 Partial Discharge Quantity pC ≤ 5 ≤ 5
Technical Data of Spring-Operated Mechanism
Component Name & Code Power Consumption (VA/W) Remarks
Closing/Locking Electromagnet Y1 See notes
First Opening Trip Unit Y2 220
Closing Trip Unit Y3 220
Overcurrent Trip Unit Y7–Y9 /
Undervoltage Trip Unit Y4 /
Trolley Locking Electromagnet Y0 3

Technical Data of Spring-Operated Mechanism

Item Unit Data
Rated Voltage V AC 220, 110; DC 220, 110
Motor Power W 90
Energy Storage Time s ≤ 8

Outline and Mounting Dimensions

Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit

 
Richiesta
+86
Fare clic per caricare il file
Scarica
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Scarica
Ottieni l'applicazione IEE-Business
Utilizza l'app IEE-Business per trovare attrezzature ottenere soluzioni connetterti con esperti e partecipare alla collaborazione dell'industria in qualsiasi momento e luogo sostenendo completamente lo sviluppo dei tuoi progetti elettrici e delle tue attività
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO