Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit

  • Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit
Atributos-chave
Marca ROCKWILL
Número do Modelo Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit
Tensão nominal 12kV
Corrente nominal 630A
Série RMR
Descrições de produtos do fornecedor
Descrição

Product Introduction

RMR‑12 Series Center‑mounted Sealed Pole Vacuum Load Break Switch‑Fuse Combination Apparatus is a new‑generation vacuum switching device developed based on unique design concepts and market demands.It is widely used in indoor armored air‑insulated switchgears.It complies with the standards including GB 3804‑2004 and GB 16926‑1997.Under normal conditions and within its technical parameters,it can operate safely and reliably in power systems of the corresponding voltage level.
Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit
Operating Environment
  • Ambient Temperature: Maximum +40°C, minimum -25°C.
  • Ambient Humidity: Daily average relative humidity ≤ 95%; monthly average relative humidity ≤ 90%.
  • Saturated Vapor Pressure: Daily average saturated vapor pressure ≤ 2.2×10⁻³ MPa; monthly average saturated vapor pressure ≤ 1.8×10⁻³ MPa.
  • Altitude: Not exceeding 1500 m.
  • Seismic Intensity: Not exceeding 8 degrees.
  • Application Site: No dripping water, no flammable or explosive hazards, no chemically corrosive gases, and no severe dust.
  • Special Note: If the product's operating environment exceeds the above specifications, users may negotiate with our company for confirmation.

Main Technical Parameters

No. Item Unit Parameter
1 Contact Opening Distance mm 8–10
2 Contact Pressure Spring Stroke mm 3–5
3 Phase-to-Phase Center Distance mm 150 / 210 / 275
4 Opening/Closing Asynchronism ms ≤ 2
5 Contact Bounce Time (Closing) ms ≤ 3
6 Average Closing Speed m/s 0.4–0.8
7 Average Opening Speed m/s 1.0–1.4
8 Closing Time (at Rated Operating Voltage) ms ≤ 60
9 Opening Time (at Rated Operating Voltage) ms ≤ 30
10 Main Circuit Resistance μΩ ≤ 250
11 Allowable Wear Thickness of Moving and Stationary Contacts mm 3

Technical Parameters

No. Item Unit RMR-12/T630-20 Vacuum Circuit Breaker RMR-12/T630-20 Vacuum Circuit Breaker – Fuse Combination Equipment
1 Rated Voltage kV 12 12
2 Power Frequency Withstand Voltage (Phase-to-Phase, Phase-to-Ground) kV 42 42
3 Lightning Impulse Withstand Voltage (Phase-to-Phase, Phase-to-Ground) kV 75 75
4 Rated Current A 630 160 (Fuse)
5 Rated Short-Circuit Breaking Current kA - 50 (Fuse)
6 Rated Short-Time Withstand Current kA 20 -
7 Rated Peak Withstand Current kA 50 -
8 Rated Closing Switching Current kA 50 -
9 Rated Cable Charging Breaking Current A 16 -
10 Rated Making Current A - 3150
11 Breaking Capacity of Transformer kVA 1600 -
12 Electrical Life Cycles 10,000 -
13 Partial Discharge Quantity pC ≤ 5 ≤ 5
Technical Data of Spring-Operated Mechanism
Component Name & Code Power Consumption (VA/W) Remarks
Closing/Locking Electromagnet Y1 See notes
First Opening Trip Unit Y2 220
Closing Trip Unit Y3 220
Overcurrent Trip Unit Y7–Y9 /
Undervoltage Trip Unit Y4 /
Trolley Locking Electromagnet Y0 3

Technical Data of Spring-Operated Mechanism

Item Unit Data
Rated Voltage V AC 220, 110; DC 220, 110
Motor Power W 90
Energy Storage Time s ≤ 8

Outline and Mounting Dimensions

Mid-mounted Solid-sealed Vacuum Load Switch-Fuse Combination Unit

 
Enviar consulta
+86
Clique para fazer upload do arquivo
Baixar
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Baixar
Obter Aplicativo Comercial IEE-Business
Use o aplicativo IEE-Business para encontrar equipamentos obter soluções conectar-se com especialistas e participar da colaboração setorial em qualquer lugar e a qualquer hora apoiando totalmente o desenvolvimento de seus projetos e negócios no setor de energia
Email
E-mail
WhatsApp
WhatsApp
Chat
Chen/CEO