占位边距

Produkte

Chinesischer Hersteller von Umschaltvorrichtungen, Transformatoren, Schaltanlagen, Ladeeinrichtungen für Elektrofahrzeuge und digitalen Stromerzeugungsanlagen IEE-Business

36kV 72.5kV Dry Air Insulated Dead Tank Vacuum Circuit Breaker(VCB)
  • 36kV 72.5kV Dry Air Insulated Dead Tank Vacuum Circuit Breaker(VCB)
Kernattribute
Marke ROCKWILL
Modellnummer 36kV 72.5kV Dry Air Insulated Dead Tank Vacuum Circuit Breaker(VCB)
Nennspannung 72.5kV
Nennstrom 2000A
Nennfrequenz 50/60Hz
Serie NVBOA
Produktbeschreibungen des Lieferanten
Beschreibung

Description

The Dry Air Insulated Dead Tank VCB was born of superb technology and abundant production experience of Meidensha Corporation.It is a circuit breaker employing vacuum interrupters and dry air for insulation. In order to use no SF6, which is global warming gas, there is no fear to decomposition of gas due to current interruption. It is therefore a highly reliable and high-performance circuit breaker.

Feature

Dead Tank Type VCB optimized for green procurement. It uses dry air for insulation in place of the SF6 which is specified as a greenhouse gas. Our basic design concept is to realize the environmental factors in design (The 3Rs (Reduce, Reuse, and Recycle) + LS (Longuse & Separable)) and life-cycle cost (LCC) reduction as basic concepts.

  • Contribution to global warming prevention

Dry air insulation are employed instead of SF6 gas insulation. GWP (Global Warning Potential) of SF6 is 23,900.

  • Excellent breaking performance

Since each current breaking section employs a vacuum interrupter, insulation recovery characteristics are excellent. It exhibits superb characteristics in cases of short-circuit interruption and short line fault interruption.

  • Sucient capability against multiple strokes and evolving faults

Since the vacuum interrupters used are of completely self-arc-diusion type, this circuit breaker is the only unit that is capable of disposing of multiple strokes and evolving fault currents.

  • Reduction of maintenance labor

Use of vacuum interrupters in the current breaking sections eliminates requirements of inspection for these sections. Therefore, man-hours can be saved for maintenance and inspection.

Type and Ratings

Specifications

Rated voltage (kV)

36

72.5

Withstand
voltage

1 min power frequency (kV rms)

70

140

1.2x50μs impulse (kV peak)

200

350

Rated frequency (Hz)

50/60

Rated normal current (A)

2000

2000/3150

Rated short circuit breaker current (kA)

31.5

40

Rated transient recovery voltage 

Rate of rise

(kV/μs))

1.19

1.47

First pole to clear factor

1.5

Rated short circuit making current (kA)

82

104

Rated short time current (kA)

31.5 (3s)

40 (3s)

Rated breaking time (cycle)

3

Rated opening time (s)

0.033

0.03

Make time with no load (s)

0.05

0.10

Operating duty

O-0.3s-CO-15s-CO

Closing control voltage (Vdc)

48, 100, 110, 125, 250

Rated tripping voltage (Vdc)

48, 100, 110, 125, 250

Supply voltage for

charging motor

(Vdc)

48, 100, 110, 125, 250

(Vac)

60, 120, 240

Rated dry-air pressure

0.5MPa-g (at 20℃ )

Closing operation system

Spring

Tripping control system

Spring

Applicable standard

IEC 62271-100-2008, ANSI/IEEE C37.06-2009

Construction

Overall construction

For each phase, a current breaking vacuum interrupter is accommodated in the grounded tank. The operation system is such that closing and tripping are effected by spring force.The operating mechanism and 3-phase interlinkage are assembled on a common base, which is installed on the frame legs.

Internal construction

The overall structure is composed mainly of grounded tank, vacuum interrupters (VI), insulating rods, bushings and main circuit terminals. Each grounded tank is filled with dry air maintained at a rated pressure of 0.5MPa-g (20℃).

Internal construction of vacuum circuit breaker

Dry air system

Outline drawing

Dimensions (72.5kV)

Dimensions (36kV)

Standard connection diagram

Performance

Performance of the circuit breaker has been designed in accordance with ANSI and IEC standard, and verified by type test. All products are shipped after confirmation of various performances by acceptance test based on these standards.

  • Withstand voltage characteristics :Performance of withstand voltage is assured at the specified dry air pressure. Even though the dry air pressure has been lowered to the alarming level, the required insulation level can be assured.In addition, even though this pressure lowers to the atmosphericpressure, the circuit breaker withstands the rated voltage.

  • Current passing performance :Since the main contacts are located under vacuum, their surfaces are never oxidized and current passing performance is therefore stabilized. In the closing mode of circuit breaker, a pressing force is exerted between main contacts by the effect of pressing spring and sufficient tolerance is assured against closing current and short-time current.

  • Mechanical life :Due to adoption of simplified operating mechanism, switching characteristics are extremely stabilized. Frequent switching performance has also been verified through continuous mechanical switching test by repeating switching operations more than 10,000 times.

  • Electrical life :Since current breaking is performed in the vacuum interrupter,arcing energy generated during current interruption is extremely low and contact erosion is minimal. This implies long contact life.Load current switching : 10,000 times

  • Rated breaking current switching : 20 times

Dokumentationsressourcenbibliothek
Dead Tank Circuit Breakers Catalog
Eingeschränkt.
Dead Tank Circuit Breakers Catalog
Produktkatalog
English
Beratung
Beratung
FAQ
Q: Was ist der Unterschied zwischen einem Vakuumschalter und einem SF-Schalter?
A:
  1. Ihr wesentlicher Unterschied liegt in den Bogenlöschmedien: Vakuumschalter verwenden ein hohes Vakuum (10⁻⁴~10⁻⁶Pa) zur Isolation und Bogenlöschung; SF₆-Schalter verlassen sich auf SF₆-Gas, das Elektronen gut absorbieren kann, um Bögen zu löschen.
  2. In Bezug auf die Spannungseignung: Vakuumschalter eignen sich für mittlere bis niedrige Spannungen (10kV, 35kV; einige bis 110kV), selten über 220kV. SF₆-Schalter sind für hohe bis ultrahohe Spannungen (110kV~1000kV) geeignet und sind im ultra-hohen Spannungsnetz der Hauptstrom.
  3. Was die Leistung betrifft: Vakuumschalter löschen Bögen schnell (<10ms), haben eine Unterbrechungskapazität von 63kA~125kA, eignen sich für häufige Nutzung (z.B. Stromverteilung) und haben eine lange Lebensdauer (>10.000 Zyklen). SF₆-Schalter zeichnen sich durch stabile Unterbrechung großer/induktiver Ströme aus, arbeiten aber seltener, da sie nach der Bogenlöschung Zeit zum Wiederherstellen der Isolation benötigen.
Q: Was sind die strukturellen Merkmale des Tank-Schalters?
A:

Einbaustruktur:

  • Einbaustruktur: Die Bogenlöschkammer, die isolierende Flüssigkeit und die zugehörigen Komponenten des Schalters sind in einem Metallbehälter versiegelt, der mit einer isolierenden Gasatmosphäre (z. B. Schwefelhexafluorid) oder isolierendem Öl gefüllt ist. Dies bildet einen relativ unabhängigen und abgeschlossenen Raum, der effektiv vor externen Umweltfaktoren schützt, die die internen Komponenten beeinflussen könnten. Diese Konstruktion verbessert die Isolationsleistung und Zuverlässigkeit der Ausrüstung, was sie für verschiedene harte Außenumgebungen geeignet macht.

Aufbau der Bogenlöschkammer:

  • Aufbau der Bogenlöschkammer: Die Bogenlöschkammer wird in der Regel innerhalb des Behälters installiert. Ihr Aufbau ist kompakt gestaltet, um eine effiziente Bogenlöschung in einem begrenzten Raum zu ermöglichen. Abhängig von verschiedenen Bogenlöschprinzipien und -technologien kann der spezifische Aufbau der Bogenlöschkammer variieren, enthält aber in der Regel wichtige Komponenten wie Kontakte, Düsen und isolierende Materialien. Diese Komponenten arbeiten zusammen, um sicherzustellen, dass der Bogen schnell und effektiv erlischt, wenn der Schalter den Strom unterbricht.

Betriebsmechanismus:

  • Betriebsmechanismus: Gängige Betriebsmechanismen umfassen federbetriebene und hydraulisch betriebene Mechanismen.

  • Federbetriebener Mechanismus: Dieser Mechanismus ist einfach im Aufbau, sehr zuverlässig und leicht zu warten. Er treibt die Öffnungs- und Schließvorgänge des Schalters durch das Speichern und Freisetzen von Energie in Federn an.

  • Hydraulisch betriebener Mechanismus: Dieser Mechanismus bietet Vorteile wie hohe Leistungsausgabe und sanfte Bewegungen, was ihn für Hochspannungs- und Hochstrom-Schalter geeignet macht.

Verwandte Produkte
Verwandte Lösungen
Anfrage senden
Herunterladen
Experts Electrical is dedicated to serving the personnel in the global power industry.
Join Experts Electrical, not only can you discover power equipment and power knowledge, but also canhnd like - minded friends!
App Store
Herunterladen
IEE-Business-Anwendung abrufen
Nutzen Sie die IEE-Business-App um Geräte zu finden Lösungen zu erhalten Experten zu kontaktieren und an Branchenkooperationen teilzunehmen jederzeit und überall zur vollen Unterstützung Ihrer Stromprojekte und Ihres Geschäfts.
Email
E-mail
WhatsApp
WhatsApp
Chat
To Boss